Where an air pressure test has not been carried out, typically in existing dwellings, uncontrolled air infiltration heat losses are estimated by the DEAP software based on:
After the number of openable sections has been identified, a record must be made of whether the openable section is draught stripped or not.
Examples of openings with and without draught stripping are shown in the table below.
Table 3.5 – Draught-stripping examples
![]() |
Example of single glazed wood window without draught stripping. |
![]() |
Example of uPVC door with draught stripping (grey coloured strip). |
If an openable section is only partially draught stripped, it should be assigned as not draught stripped. An incomplete length of draught stripping would not create a seal to the openable section.
Errors typically identified during BER audits are as follows:
The images in the table below show typical openings found in dwellings. The total number of openable sections to be assessed for draught stripping is identified in each case.
Table 3.6 – Opening types - examples
| Image | Description | Total number of openable sections considered for draught stripping. |
|---|---|---|
![]() |
uPVC double glazed door with side windows. | 1 |
![]() |
uPVC double glazed window. Upper right and lower right sections are openable. | 2 |
![]() |
Wood fully glazed door. | 1 |
![]() |
uPVC patio doors. Both sides openable. | 2 |
![]() |
Loft hatch with fold down ladder | 1 |
![]() |
uPVC wrap around window. Openable sections to left and right sides. | 2 |
![]() |
Wood single glazed window. Openable sections to top right and top left. | 2 |
![]() |
Access door to crawl space (room-in-roof) | 1 |
![]() |
Metal frame double glazed window. No openable sections. | 0 |